T5N 630 TMA 500-5000 4p F F

Product ID:75672
Updated: 2026/4/10
ABB T5N 630 TMA 500-5000 4p F F

Key Features

  • 1Deliver a 500 A main circuit current rating for robust power distribution. 2、Ensure reliable operation with a thermal magnetic trip mechanism. 3、Meet IEC standards for guaranteed safety and performance compliance. 4、Achieve 5000 electrical cycles at 60 cycles per hour for durability. 5、Withstand 20,000 mechanical cycles at 120 cph for longevity.
Product Details
T5N 630 TMA 500-5000 4p F F
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
9AKK10103A1056 9AKK108467A6707
Product Net Width
186 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
5.1 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
5000 cycle 60 cycles per hour
Mechanical Durability
20000 cycle 120 cycles per hour
Number of Poles
4
Power Loss
at Rated Operating Conditions per Pole 28.8 W
Rated Current (In)
500 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 70 kA (230 V AC) 70 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 30 kA (500 V AC) 25 kA (690 V AC) 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 70 kA (230 V AC) 70 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 30 kA (500 V AC) 25 kA (690 V AC) 20 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 25 kA (750 V DC) 3 Poles in Series 16 kA
Rated Uninterrupted Current (Iu)
630 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers Front
Test Voltage Max (Utest)
3500 V
Test Voltage at Industrial Frequency for 1 Minute
3500 V
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA054459R1

Specifications may be subject to change without notice