T5S 400 PR222DS/P-LSIG In=400 4p F F
Product ID:75157
Updated: 2026/4/10

Key Features
- 1Handle main circuit currents up to 400 Amperes. 2、Withstand short-circuit currents as high as 50 kA. 3、Achieve electrical durability of 7000 cycles and mechanical durability of 20,000 cycles. 4、Meet stringent IEC standards and EU RoHS directives for compliance. 5、Suit various AC voltages including 220V, 230V, 380V, and 400V.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK10103A1056 9AKK108467A6707 | Product Net Width | 186 mm |
| Product Net Height | 205 mm | Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 6.2 kg | Product Main Type | SACE Tmax T |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Suitable For | T5 | Suitable for Product Class | Moulded Case Circuit Breakers |
| Version | F | Electrical Durability | 7000 cycle 60 cycles per hour |
| Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 4 |
| Power Loss | at Rated Operating Conditions per Pole 16.5 W | Rated Current (In) | 400 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 40 kA (500 V AC) 30 kA (690 V AC) 25 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 5 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 40 kA (500 V AC) 30 kA (690 V AC) 25 kA |
| Rated Uninterrupted Current (Iu) | 400 A | Release | PR222DS/P-LSIG |
| Release Type | EL | Short-Circuit Performance Level | S |
| Standards | IEC | Sub-type | T5 |
| Terminal Connection Type | Fixed Circuit-Breakers Front | Test Voltage Max (Utest) | 3500 V |
| Test Voltage at Industrial Frequency for 1 Minute | 3500 V | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
| UNSPSC | 39121100 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA054347R1 |
Specifications may be subject to change without notice
