T5V 400 PR221DS-LS/I In=320 4p F F
Product ID:74222
Updated: 2026/4/9

Key Features
- 1Deliver reliable electrical protection in demanding industrial environments. 2、Utilize solid-state release technology for fast, precise circuit interruption. 3、Simplify installation and maintenance with accessible front terminals. 4、Ensure long service life with up to 20,000 mechanical cycles. 5、Meet environmental standards with EU RoHS Directive 2011/65/EU compliance.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK10103A1056 9AKK108467A6707 | Product Net Width | 186 mm |
| Product Net Height | 205 mm | Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 6.2 kg | Product Main Type | SACE Tmax T |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Suitable For | T5 | Suitable for Product Class | Moulded Case Circuit Breakers |
| Version | F | Electrical Durability | 7000 cycle 60 cycles per hour |
| Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 4 |
| Power Loss | at Rated Operating Conditions per Pole 10.6 W | Rated Current (In) | 320 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 200 kA (400 V AC) 200 kA (415 V AC) 200 kA (440 V AC) 180 kA (500 V AC) 150 kA (690 V AC) 80 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 5 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 200 kA (400 V AC) 200 kA (415 V AC) 200 kA (440 V AC) 180 kA (500 V AC) 150 kA (690 V AC) 80 kA |
| Rated Uninterrupted Current (Iu) | 400 A | Release | PR221DS-LS/I |
| Release Type | EL | Short-Circuit Performance Level | V |
| Standards | IEC | Sub-type | T5 |
| Terminal Connection Type | Fixed Circuit-Breakers Front | Test Voltage Max (Utest) | 3500 V |
| Test Voltage at Industrial Frequency for 1 Minute | 3500 V | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
| UNSPSC | 39121100 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA054388R1 |
Specifications may be subject to change without notice