T6H 800 UL/CSA BREAKING PART 4p F F

Product ID:92375
Updated: 2026/4/4
ABB T6H 800 UL/CSA BREAKING PART 4p F F

Key Features

  • 1Achieve high short-circuit breaking capacity of 65 kA at 400V. 2、Meet strict UL/CSA safety standards for North America. 3、Utilize robust construction with fixed built-in technique. 4、Access easy front terminal connections for main circuits. 5、Integrate a complete protection unit for comprehensive safety.
Product Details
T6H 800 UL/CSA BREAKING PART 4p F F
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
9.5 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Breaking Part
Suitable For
T6
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Mechanical Durability
20000 cycle 120 cycles per hour
Number of Poles
4P
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
600 V AC 600 V DC
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 200 kA (480 V AC) 65 kA (600 V AC) 35 kA (500 V DC) 2 Poles in Series 50 kA (600 V DC) 3 Poles in Series 35 kA
Rated Uninterrupted Current (Iu)
800 A
Short-Circuit Performance Level
H
Standards
UL
Sub-type
T6
Terminal Connection Type
Fixed Circuit-Breakers Front
Test Voltage Max (Utest)
3500 V
Interrupting Rating acc. to UL489
(240 V AC) 200 kA (480 V AC) 65 kA (600 V AC) 35 kA (500 V DC) 2 Poles in Series 50 kA (600 V DC) 3 Poles in Series 35 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA061721R1

Specifications may be subject to change without notice