T6L 630 DC TMD1134/3402 F F 4P
Product ID:87741
Updated: 2026/4/8

Key Features
- 1Ensure reliable high-current DC power distribution with a 1134A rating. 2、Enhance safety using front terminals with thermomagnetic release (TMD). 3、Achieve stable operation via a robust fixed four-pole design. 4、Meet stringent Uimp standards for superior impulse voltage withstand. 5、Reduce maintenance costs and downtime with durable, certified construction.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK10103A1058 | Product Net Width | 280 mm |
| Product Net Height | 268 mm | Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 12 kg | Product Name | Moulded Case Circuit Breaker |
| Product Type | CB | Version | F |
| Current Type | DC | Electrical Durability | 2000 cycle 20 cycles per hour |
| Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 4P |
| Power Loss | at Rated Operating Conditions per Pole 30.6 W | Rated Current (In) | 1134 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 500 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (500 V DC) 2 Poles in Series 65 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (500 V DC) 2 Poles in Series 65 kA | Rated Uninterrupted Current (Iu) | 1134 A |
| Release | TMD | Release Type | TM |
| Short-Circuit Performance Level | L | Standards | GB/T 14048.2 |
| Sub-type | T6 | Terminal Connection Type | Fixed Circuit-Breakers |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | Manufacturer ID | 2TFC000966R1001 |
Specifications may be subject to change without notice