T6L 630 TMA 630-6300 4p F F InN=100%In
Product ID:75079
Updated: 2026/4/10

Key Features
- 1Deliver 150kA @ 220V AC interrupting capacity for robust short-circuit protection. 2、Ensure safe operation with reliable thermal and magnetic trip mechanisms. 3、Support compatibility with 690V AC and 750V DC systems. 4、Provide endurance for 7000 cycles at 60 cycles per hour. 5、Meet CE and IEC certifications for global approval and use.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK10103A1058 9AKK108467A6707 | Product Net Width | 280 mm |
| Product Net Height | 268 mm | Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 12 kg | Product Main Type | SACE Tmax T |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Suitable For | T6 | Suitable for Product Class | Moulded Case Circuit Breakers |
| Version | F | Electrical Durability | 7000 cycle 60 cycles per hour |
| Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 4 |
| Power Loss | at Rated Operating Conditions per Pole 30.6 W | Rated Current (In) | 630 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC 750 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA (230 V AC) 150 kA (380 V AC) 75 kA (400 V AC) 75 kA (415 V AC) 75 kA (440 V AC) 60 kA (500 V AC) 49 kA (690 V AC) 22.5 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 7.6 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 100 kA (400 V AC) 100 kA (415 V AC) 100 kA (440 V AC) 80 kA (500 V AC) 65 kA (690 V AC) 30 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 2 Poles in Series 65 kA (750 V DC) 3 Poles in Series 50 kA |
| Rated Uninterrupted Current (Iu) | 630 A | Release | TMA |
| Release Type | TM | Short-Circuit Performance Level | L |
| Standards | IEC | Sub-type | T6 |
| Terminal Connection Type | Fixed Circuit-Breakers Front | Test Voltage Max (Utest) | 3500 V |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q | UNSPSC | 39121100 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
| Manufacturer ID | 1SDA060213R1 |
Specifications may be subject to change without notice