T6L 800 PR221DS-I In=800 3p F F
Product ID:74114
Updated: 2026/4/9

Key Features
- 1Handle up to 800A for demanding industrial applications. 2、Utilize solid-state release technology for reliable, precise protection. 3、Simplify installation and maintenance with accessible front terminals. 4、Ensure compliance with international safety and performance standards. 5、Reduce total cost of ownership through durable design and easy serviceability.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK10103A1058 9AKK108467A6707 | Product Net Width | 210 mm |
| Product Net Height | 268 mm | Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 9.5 kg | Product Main Type | SACE Tmax T |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Suitable For | T6 | Suitable for Product Class | Moulded Case Circuit Breakers |
| Version | F | Electrical Durability | 5000 cycle 60 cycles per hour |
| Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 3 |
| Power Loss | at Rated Operating Conditions per Pole 32 W | Rated Current (In) | 800 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA (230 V AC) 150 kA (380 V AC) 75 kA (400 V AC) 75 kA (415 V AC) 75 kA (440 V AC) 60 kA (500 V AC) 49 kA (690 V AC) 22.5 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 10 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 100 kA (400 V AC) 100 kA (415 V AC) 100 kA (440 V AC) 80 kA (500 V AC) 65 kA (690 V AC) 30 kA |
| Rated Uninterrupted Current (Iu) | 800 A | Release | PR221DS-I |
| Release Type | EL | Short-Circuit Performance Level | L |
| Standards | IEC | Sub-type | T6 |
| Terminal Connection Type | Fixed Circuit-Breakers Front | Test Voltage Max (Utest) | 3500 V |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q | UNSPSC | 39121100 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
| Manufacturer ID | 1SDA060300R1 |