T6N 630 PR221DS-LS/I In=630 4p F F

Product ID:74400
Updated: 2026/7/21
ABB T6N 630 PR221DS-LS/I In=630 4p F F

Key Features

  • 1Achieve 70 kA interrupting capacity for maximum safety.
  • 2Utilize thermal-magnetic and solid-state trip for reliable protection.
  • 3Endure 7000 electrical and 20000 mechanical cycles.
  • 4Integrate easily with compact 103.5 x 280 x 268 mm dimensions.
  • 5Meet global standards with IEC and CE certifications.

Need price and lead time?

Request a quote for original ABB T6N 630 PR221DS-LS/I In=630 4p F F. Tell us your required quantity.

It only takes 1 minute — get your quotation and delivery time.
Quote within 24h
100% Original ABB
Global Delivery
No Spam · Secure

Need a quote? Enter your quantity and get pricing fast.

Qty

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
9AKK10103A1058 9AKK108467A6707
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
12.415 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T6
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
7000 cycle 60 cycles per hour
Mechanical Durability
20000 cycle 120 cycles per hour
Number of Poles
4
Power Loss
at Rated Operating Conditions per Pole 20 W
Rated Current (In)
630 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 70 kA (230 V AC) 70 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 30 kA (500 V AC) 25 kA (690 V AC) 15 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 7.6 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 70 kA (230 V AC) 70 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 30 kA (500 V AC) 25 kA (690 V AC) 20 kA
Rated Uninterrupted Current (Iu)
630 A
Release
PR221DS-LS/I
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
T6
Terminal Connection Type
Fixed Circuit-Breakers Front
Test Voltage Max (Utest)
3500 V
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA060231R1

Specifications may be subject to change without notice

Still deciding on T6N 630 PR221DS-LS/I In=630 4p F F?

Our engineers can confirm stock, price, and lead time for this ABB part.

Get a no-obligation quote in 1 minute.

Chat with us