T6N 630 PR222DS/P-LSI In=630 3p F F

Product ID:75154
Updated: 2026/4/10
ABB T6N 630 PR222DS/P-LSI In=630 3p F F

Key Features

  • 1Ensure reliable protection with 36kA short-circuit breaking capacity at 380V AC. 2、Detect faults precisely using the advanced LSIG electronic trip unit. 3、Achieve long-lasting performance with 20,000 mechanical and 7,000 electrical cycles. 4、Fit various installation spaces with compact 268x210x103.5mm dimensions. 5、Meet IEC 60947 standards for safety and reliability in installations.
Product Details
T6N 630 PR222DS/P-LSI In=630 3p F F
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
9AKK10103A1058 9AKK108467A6707
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
9.5 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T6
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
7000 cycle 60 cycles per hour
Mechanical Durability
20000 cycle 120 cycles per hour
Number of Poles
3
Power Loss
at Rated Operating Conditions per Pole 20 W
Rated Current (In)
630 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 70 kA (230 V AC) 70 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 30 kA (500 V AC) 25 kA (690 V AC) 15 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 7.6 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 70 kA (230 V AC) 70 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 30 kA (500 V AC) 25 kA (690 V AC) 20 kA
Rated Uninterrupted Current (Iu)
630 A
Release
PR222DS/P-LSI
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
T6
Terminal Connection Type
Fixed Circuit-Breakers Front
Test Voltage Max (Utest)
3500 V
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA060228R1

Specifications may be subject to change without notice