T6N800 MCP-UL/CSA PR221DS-I In=800 3p FF
Product ID:90882
Updated: 2026/4/6

Key Features
- 1Handle robust 800A rated current for demanding applications. 2、Meet UL and CSA safety and reliability standards with certification. 3、Ensure safe operation via an efficient magnetic release mechanism. 4、Simplify installation with convenient front terminal connections. 5、Achieve long-lasting performance with a 20,000-cycle durable design.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK10103A1058 9AKK108467A6707 | Product Net Width | 210 mm |
| Product Net Height | 268 mm | Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 9.5 kg | Product Main Type | SACE Tmax T |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Suitable For | T6 | Suitable for Product Class | Moulded Case Circuit Breakers |
| Version | F | Mechanical Durability | 20000 cycle 120 cycles per hour |
| Number of Poles | 3P | Power Loss | at Rated Operating Conditions per Pole 32 W |
| Rated Current (In) | 800 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 600 V AC |
| Rated Uninterrupted Current (Iu) | 800 A | Release | PR221DS-I |
| Release Type | EL | Short-Circuit Performance Level | N |
| Standards | UL | Sub-type | T6 |
| Terminal Connection Type | Fixed Circuit-Breakers Front | Test Voltage Max (Utest) | 3500 V |
| Interrupting Rating acc. to UL489 | (240 V AC) 65 kA (480 V AC) 35 kA (600 V AC) 20 kA | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA061706R1 |
Specifications may be subject to change without notice