T6V 630 TMA 630-6300 4p F F InN=100%In

Product ID:92155
Updated: 2026/4/4
ABB T6V 630 TMA 630-6300 4p F F InN=100%In

Key Features

  • 1Deliver reliable performance with a high-rated current of 630 amps. 2、Ensure safe operation using a thermomagnetic release mechanism. 3、Provide robust insulation for up to 1000 volts rated voltage. 4、Safeguard industrial systems with a 50kA short-circuit performance level. 5、Meet IEC standards for electrical durability and operational safety.
Product Details
T6V 630 TMA 630-6300 4p F F InN=100%In
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
9AKK10103A1058 9AKK108467A6707
Product Net Width
280 mm
Product Net Height
268 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
12 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T6
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
7000 cycle 60 cycles per hour
Mechanical Durability
20000 cycle 120 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 30.6 W
Rated Current (In)
630 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 120 kA (400 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 65 kA (690 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 7.6 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 150 kA (400 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 120 kA (500 V AC) 85 kA (690 V AC) 40 kA (500 V DC) 2 Poles in Series 70 kA (750 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
630 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
V
Standards
IEC
Sub-type
T6
Terminal Connection Type
Fixed Circuit-Breakers Front
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA069416R1

Specifications may be subject to change without notice