UA16-30-10 190V 50Hz / 220V 60Hz
Product ID:88154
Updated: 2026/4/4

Key Features
- 1Achieve up to 250,000 electrical cycles for high durability. 2、Handle peak capacitor switching currents exceeding 100x In. 3、Operate across versatile 190V 50Hz and 220V 60Hz ranges. 4、Rely on robust screw terminals and IP20 enclosure protection. 5、Meet IEC 60947-4-1 and VDE 0110 safety standards.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product Net Width | 44 mm | Product Net Depth / Length | 74 mm |
| Product Net Height | 74 mm | Product Net Weight | 0.34 kg |
| Number of Main Contacts NO | 3 | Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 | Number of Auxiliary Contacts NC | 0 |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1 | Rated Operational Voltage | Auxiliary Circuit 690 V Main Circuit 690 V |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz Control Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz | Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-5-1, Π= 40 °C 16 A |
| Rated Operational Power AC-6b (Pe) | (230 / 240 V) 40 °C, 50 / 60 Hz 7.5 kvar (230 / 240 V) 55 °C, 50 / 60 Hz 6.7 kvar (230 / 240 V) 70 °C, 50 / 60 Hz 6 kvar (400 / 415 V) 40 °C, 50 / 60 Hz 12.5 kvar (400 / 415 V) 70 °C, 50 / 60 Hz 10 kvar (400 / 415 V) 55 °C, 50 / 60 Hz 11.7 kvar (440 V) 40 °C, 50 / 60 Hz 13.7 kvar (440 V) 55 °C, 50 / 60 Hz 13 kvar (440 V) 70 °C, 50 / 60 Hz 11 kvar (500 / 550 V), 40 °C, 50 / 60 Hz 15.5 kvar (500 / 550 V) 55 °C, 50 / 60 Hz 14.7 kvar (500 / 550 V) 70 °C, 50 / 60 Hz 12.5 kvar (690 V) 40 °C, 50 / 60 Hz 21.5 kvar (690 V) 55 °C, 50 / 60 Hz 20 kvar (690 V) 70 °C, 50 / 60 Hz 17 kvar | Rated Operational Current AC-15 (Ie) | (500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (380 / 400 V) 3 A |
| Short-Circuit Protective Devices | Auxiliary Circuit - gG Type Fuses 10 A gG Type Fuses 1.5 ... 1.8 A | Rated Short-time Withstand Current Low Voltage (Icw) | for 0.1 s 140 A for 1 s 100 A |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A | Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W (48 V) 2.8 A / 134 W (72 V) 2 / 144 W (110 V) 1.1 A / 121 W (125 V) 1.1 / 138 W (220 V) 0.55 A / 121 W (250 V) 0.55 / 138 W |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 1000 V acc. to IEC 60947-5-1 690 V acc. to UL/CSA 600 V | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour | Rated Control Circuit Voltage (Uc) | 50 Hz 190 V 60 Hz 220 V |
| Coil Consumption | Average Holding Value 50 Hz 8 V·A Average Holding Value 60 Hz 8 V·A Average Pull-in Value 50 Hz 70 V·A Average Pull-in Value 60 Hz 80 V·A | Operate Time | Between Coil De-energization and NO Contact Opening 4 ... 11 ms Between Coil Energization and NO Contact Closing 10 ... 26 ms |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | Mounting by Screws (not supplied) | 2 x M4 screws placed diagonally |
| Connecting Capacity Main Circuit | Flexible with Cable End 1/2x 0.75 ... 2.5 mm² Rigid Solid 1/2x 1 ... 4 mm² | Connecting Capacity Auxiliary Circuit | Flexible with Cable End 1/2x 0.75 ... 2.5 mm² Rigid Solid 1/2x 1 ... 4 mm² |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 | Connecting Terminals (delivered in open position) Main Poles | M 3.5 (+,-) pozidriv 2 screws with cable clamp |
| Terminal Type | Screw Terminals | Connecting Capacity Main Circuit UL/CSA | 1/2x 18-10 AWG |
| Tightening Torque UL/CSA | Auxiliary Circuit 9 in·lb Control Circuit 9 in·lb Main Circuit 9 in·lb | Ambient Air Temperature | Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °C Near Contactor for Operation in Free Air (Uc) -40 ... 70 °C |
| Climatic Withstand | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II | Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Object Classification Code | Q | ETIM 7 | EC001079 - Capacitor contactor |
| ETIM 8 | EC001079 - Capacitor contactor | ETIM 9 | EC001079 - Capacitor contactor |
| eClass | V11.0 : 27371006 | UNSPSC | 39121529 |
| Manufacturer ID | 1SBL181022R3610 |
Specifications may be subject to change without notice