XT1C160 TMD100/1000 FFC 4P
Product ID:70665
Updated: 2026/4/4

Key Features
- 1Deliver high-rated current capacity up to 100 A for demanding loads. 2、Provide adjustable thermal-magnetic protection for precise overload safety. 3、Ensure robust short-circuit interruption with capacities to 40 kA. 4、Guarantee reliable 50/60 Hz operation across diverse networks. 5、Simplify installation using the compact front-access terminal design.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Version | F | Current Type | AC/DC |
| Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
| Number of Poles | 4P | Power Loss | at Rated Operating Conditions per Pole 7.0 W |
| Rated Current (In) | 100 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 800 V | Rated Operational Voltage | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 12.5 kA (500 V AC) 9 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA |
| Rated Uninterrupted Current (Iu) | 160 A | Release | TMD |
| Release Type | TM | Short-Circuit Performance Level | C |
| Standards | IEC60947-2 GB/T 14028.2 | Sub-type | XT1 |
| Terminal Connection Type | Front for Copper Cables | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Manufacturer ID | 2TFH100067R1001 |
Specifications may be subject to change without notice