XT1C160 TMD160/1600 FFC 4P N=100%

Product ID:92242
Updated: 2026/4/4
ABB XT1C160 TMD160/1600 FFC 4P N=100%

Key Features

  • 1Withstand 120 cycles per hour and 8,000 cycles for long-lasting performance. 2、Feature a TMD release for reliable operation under various conditions. 3、Suit applications requiring four poles to enhance system efficiency and safety. 4、Support up to 690V AC and 500V DC for versatile voltage requirements. 5、Meet international safety and performance standards for global compliance.
Product Details
XT1C160 TMD160/1600 FFC 4P N=100%
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC/DC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 15 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 12.5 kA (500 V AC) 9 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
C
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Front for Copper Cables
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100071R1001

Specifications may be subject to change without notice