ABB XT1N160 TMD160/1600 FFC 4P+RC Inst

Key Features

  • 1Protect transformers and generators with high-performance circuit breaker. 2、Ensure reliable operation with 160 A rated current. 3、Achieve superior insulation via 8 kV impulse withstand voltage. 4、Clear faults efficiently using 50 kA short-circuit breaking capacity. 5、Operate safely with thermomagnetic release (TMD).
Product Details
XT1N160 TMD160/1600 FFC 4P+RC Inst
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
2.7 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4
Power Loss
at Rated Operating Conditions per Pole 15 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 18 kA (500 V AC) 15 kA (525 V AC) 11 kA (690 V AC) 5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 22 kA (690 V AC) 6 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
N
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Front for Copper Cables
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100498R1001

Specifications may be subject to change without notice