XT1N 160 TMF 16-450 3p F F
Product ID:84845
Updated: 2026/4/10

Key Features
- 1Handle high currents up to 160A efficiently. 2、Ensure safety with reliable thermomagnetic release (TMF). 3、Simplify installation using front terminal connections (F). 4、Meet IEC standards for durability and compliance. 5、Save panel space with compact 76.2x130x70 mm dimensions.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Net Width | 76.2 mm |
| Product Net Height | 130 mm | Product Net Depth / Length | 70 mm |
| Product Net Weight | 1 kg | Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker | Version | F |
| CAD Dimensional Drawing | 1SDH001295R0008 | Current Type | AC/DC |
| Electrical Durability | 120 cycles per hour 8000 cycle | Mechanical Durability | 240 cycles per hour 25000 cycle |
| Number of Poles | 3P | Opening Time | CB with SOR 15 ms CB with UVR 15 ms |
| Order Multiple | 1 piece | Rated Current (In) | 16 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Instantaneous Short-Circuit Current Setting (Ii) | 450 A |
| Rated Insulation Voltage (Ui) | 800 V | Rated Operational Voltage | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 18 kA (500 V AC) 15 kA (525 V AC) 11 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 22 kA (690 V AC) 6 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
| Rated Uninterrupted Current (Iu) | 160 A | Rated Voltage (Ur) | 690 V |
| Release | TMF | Release Type | TM |
| Setting Range | 16 A | Short-Circuit Performance Level | N |
| Standards | IEC60947-2 | Sub-type | XT1 |
| Terminal Connection Type | Front | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA080827R1 |
Specifications may be subject to change without notice