- 1Handle both AC and DC currents for versatile system integration. 2、Utilize thermomagnetic release for efficient short-circuit protection. 3、Withstand 120 cycles per hour and 8000 total cycles for durability. 4、Fit into tight spaces with compact 130x143x135 mm dimensions. 5、Meet IEC standards and CE compliance for global safety.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Net Width | 101.6 mm |
| Product Net Height | 130 mm | Product Net Depth / Length | 70 mm |
| Product Net Weight | 1.4 kg | Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker | Version | F |
| CAD Dimensional Drawing | 1SDH001295R0080 | Connecting Capacity Main Circuit | Busbar 45.5 ... 80 mm² |
| Current Type | AC/DC | Electrical Durability | 120 cycles per hour 8000 cycle |
| Mechanical Durability | 240 cycles per hour 25000 cycle | Number of Poles | 4P |
| Opening Time | CB with SOR 15 ms CB with UVR 15 ms | Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 10.7 W | Rated Current (In) | 125 A |
| Rated Frequency (f) | 50 / 60 Hz | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii) | 1250 A | Rated Insulation Voltage (Ui) | 800 V |
| Rated Operational Voltage | 690 V AC 500 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 80 kA (230 V AC) 80 kA (240 V AC) 80 kA (380 V AC) 50 kA (415 V AC) 37.5 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 17.5 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 35 kA (690 V AC) 8 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA | Rated Uninterrupted Current (Iu) | 160 A |
| Rated Voltage (Ur) | 690 V | Recommended Screw Driver | Main Circuit M6 |
| Release | TMD | Release Type | TM |
| Setting Range | 87.5...125 A | Short-Circuit Performance Level | S |
| Standards | IEC60947-2 | Sub-type | XT1 |
| Terminal Connection Type | Front | Terminal Type | Bolt |
| Tightening Torque | 6 N·m | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
| UNSPSC | 39120000 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA067445R1 |
Specifications may be subject to change without notice