Key Features
- 1Deliver up to 63.75 kA at 220-240 V AC and 50 kA at 380 V AC. 2、Ensure reliable and fast tripping under fault conditions. 3、Simplify installation with front terminals for efficient wiring. 4、Meet international standards for safety and performance. 5、Optimize panel space with compact dimensions of 76.2 mm x 130 mm x 70 mm.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Version | F | Current Type | AC/DC |
| Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
| Number of Poles | 3P | Power Loss | at Rated Operating Conditions per Pole 15 W |
| Rated Current (In) | 160 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 800 V | Rated Operational Voltage | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 63.75 kA (230 V AC) 63.75 kA (240 V AC) 63.75 kA (380 V AC) 50 kA (415 V AC) 37.5 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 17.5 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 35 kA (690 V AC) 8 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA |
| Rated Uninterrupted Current (Iu) | 160 A | Release | TMD |
| Release Type | TM | Remarks | ATLAS |
| Short-Circuit Performance Level | S | Standards | IEC60947-2 GB/T 14028.2 |
| Sub-type | XT1 | Terminal Connection Type | Front Extended |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | Manufacturer ID | 2TFH100126R1001 |
Specifications may be subject to change without notice