XT1S160 TMD63/630 FFC 4P
Product ID:91105
Updated: 2026/4/6

Key Features
- 1Ensure reliable operation in demanding power distribution environments. 2、Utilize thermal-magnetic release for safe operation under various loads. 3、Install easily with front terminals to enhance system efficiency. 4、Apply across 690V AC and 500V DC systems for versatility. 5、Withstand up to 8000 electrical cycles for long-term reliability.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Version | F | Current Type | AC/DC |
| Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
| Number of Poles | 4P | Power Loss | at Rated Operating Conditions per Pole 4.3 W |
| Rated Current (In) | 63 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 800 V | Rated Operational Voltage | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 63.75 kA (230 V AC) 63.75 kA (240 V AC) 63.75 kA (380 V AC) 50 kA (415 V AC) 37.5 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 17.5 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 35 kA (690 V AC) 8 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA |
| Rated Uninterrupted Current (Iu) | 160 A | Release | TMD |
| Release Type | TM | Short-Circuit Performance Level | S |
| Standards | IEC60947-2 GB/T 14028.2 | Sub-type | XT1 |
| Terminal Connection Type | Front for Copper Cables | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Manufacturer ID | 2TFH100142R1001 |
Specifications may be subject to change without notice