XT1S 160 TMF 20-450 4p F F
Product ID:87797
Updated: 2026/4/8

Key Features
- 1Ensure reliable operation with high-performance design for electrical systems. 2、Protect circuits safely using thermomagnetic release technology. 3、Simplify installation and maintenance with front terminal connections. 4、Meet international safety standards through full IEC compliance. 5、Extend service life with 8000-cycle electrical durability.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Net Width | 101.6 mm |
| Product Net Height | 130 mm | Product Net Depth / Length | 70 mm |
| Product Net Weight | 1.3 kg | Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker | Version | F |
| CAD Dimensional Drawing | 1SDH001295R0080 | Current Type | AC/DC |
| Electrical Durability | 120 cycles per hour 8000 cycle | Mechanical Durability | 240 cycles per hour 25000 cycle |
| Number of Poles | 4P | Opening Time | CB with SOR 15 ms CB with UVR 15 ms |
| Order Multiple | 1 piece | Rated Current (In) | 20 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Instantaneous Short-Circuit Current Setting (Ii) | 450 A |
| Rated Insulation Voltage (Ui) | 800 V | Rated Operational Voltage | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 80 kA (230 V AC) 80 kA (240 V AC) 80 kA (380 V AC) 50 kA (415 V AC) 37.5 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 17.5 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 35 kA (690 V AC) 8 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA |
| Rated Uninterrupted Current (Iu) | 160 A | Rated Voltage (Ur) | 690 V |
| Release | TMF | Release Type | TM |
| Setting Range | 20 A | Short-Circuit Performance Level | S |
| Standards | IEC60947-2 | Sub-type | XT1 |
| Terminal Connection Type | Front | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA080846R1 |
Specifications may be subject to change without notice