XT2H 125 Ekip Dip LSI In=125A 4p F F UL/CSA
Product ID:87599
Updated: 2026/4/8

Key Features
- 1Deliver high-performance protection against overloads and short circuits with adjustable settings. 2、Utilize an electronic trip unit for precise and instantaneous protection up to 125A. 3、Meet stringent safety standards with UL and CSA certifications. 4、Simplify installation with flexible ring-lug or bar connection options. 5、Ensure long-lasting performance with a design rated for 25,000 no-load operations.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product Net Width | 120 mm | Product Net Height | 130 mm |
| Product Net Depth / Length | 82.5 mm | Product Net Weight | 1.6 kg |
| Circuit Breaker Type to be Associated | Power Distribution | Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Version | F | CAD Dimensional Drawing | 1SDH002230A1002 |
| Current Type | AC | Electrical Durability | 120 cycles per hour 8000 cycle |
| Mechanical Durability | 240 cycles per hour 25000 cycle | Number of Poles | 4P |
| Power Loss | at Rated Operating Conditions per Pole 6.60 W | Rated Current (In) | 125 A |
| Rated Frequency (f) | 50/60 Hz | Rated Insulation Voltage (Ui) | 1000 V AC |
| Rated Operational Voltage | 690 V AC | Rated Uninterrupted Current (Iu) | 160 A |
| Rated Voltage (Ur) | 690 V AC | Release | Ekip Dip LSI |
| Release Type | EL | Short-Circuit Performance Level | H |
| Standards | UL | Sub-type | XT2 |
| Interrupting Rating acc. to UL489 | (240 V AC) 150 A (480 V AC) 65 A (600 V AC) 25 A | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Manufacturer ID | 1SDA102136R1 |
Specifications may be subject to change without notice