XT2H160 MF4/56 PMP 3P
Product ID:70004
Updated: 2026/4/3

Key Features
- 1Achieve reliable short-circuit protection with a high breaking capacity of up to 70 kA. 2、Ensure precise control using its 4 A rated current. 3、Simplify installation and maintenance via front terminal connections. 4、Benefit from automatic overcurrent tripping with the magnetic release. 5、Meet safety standards with compliance to IEC and EN60947.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Version | P | Current Type | AC/DC |
| Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
| Number of Poles | 3 | Power Loss | at Rated Operating Conditions per Pole 2.8 W |
| Rated Current (In) | 4 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 30 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 3 Poles in Series 70 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 30 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 3 Poles in Series 70 kA |
| Rated Uninterrupted Current (Iu) | 160 A | Release | MF |
| Release Type | M | Remarks | ATLAS |
| Short-Circuit Performance Level | H | Standards | IEC60947-2 GB/T 14028.2 |
| Sub-type | XT2 | Terminal Connection Type | Plug-In Circuit-Breakers |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | Manufacturer ID | 2TFH100674R1001 |
Specifications may be subject to change without notice