Key Features
- 1Handle up to 100 kA short-circuit current at various voltages. 2、Ensure reliable protection with a 35-50 A adjustable setting range. 3、Suit multiple applications in electrical distribution systems seamlessly. 4、Meet international IEC and UL standards for safety. 5、Withstand 120 operations per hour and 8000 total mechanical cycles.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Version | W | Current Type | AC/DC |
| Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
| Number of Poles | 4P | Power Loss | at Rated Operating Conditions per Pole 4.7 W |
| Rated Current (In) | 50 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 690 V AC 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 30 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 3 Poles in Series 70 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 30 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 3 Poles in Series 70 kA |
| Rated Uninterrupted Current (Iu) | 160 A | Release | TMA |
| Release Type | TM | Remarks | ATLAS |
| Short-Circuit Performance Level | H | Standards | IEC60947-2 GB/T 14028.2 |
| Sub-type | XT2 | Terminal Connection Type | Withdrawable Circuit-Breakers |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | Manufacturer ID | 2TFH102108R1001 |
Specifications may be subject to change without notice