XT2L 125 BREAKING PART 3p F F UL/CSA

Product ID:85545
Updated: 2026/4/10
ABB XT2L 125 BREAKING PART 3p F F UL/CSA

Key Features

  • 1Distribute 125 A of reliable power. 2、Suit three-phase systems with front terminals. 3、Meet stringent UL and CSA safety standards. 4、Enhance safety with an advanced trip mechanism. 5、Save space with compact dimensions for easy installation.
Product Details
XT2L 125 BREAKING PART 3p F F UL/CSA
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
0.82 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Breaking Part
Suitable for Product Class
SACE Tmax XT
Version
F
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Rated Operational Voltage
600 V AC 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
600 V
Short-Circuit Performance Level
L
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Interrupting Rating acc. to UL489
(240 V AC) 200 kA (480 V AC) 100 kA (600 V AC) 35 kA (250 V DC) 2 Poles in Series 75 kA (500 V DC) 3 Poles in Series 75 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA075633R1

Specifications may be subject to change without notice