XT2L 160 Ekip C Dip LSI R160 F F 3P
Product ID:71016
Updated: 2026/4/4

Key Features
- 1Break short circuits up to 150 kA at 240V AC for robust protection. 2、Utilize a solid-state Ekip release for enhanced reliability and durability. 3、Meet IEC standards and EU RoHS directives for guaranteed safety and compliance. 4、Protect transformers, generators, and installations across diverse applications. 5、Ensure reliable operation in AC power distribution systems with front terminals.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 1SDL000190R0001 | Product Net Width | 90 mm |
| Product Net Height | 130 mm | Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 1.2 kg | Product Name | Moulded Case Circuit Breaker |
| Product Type | CB | Version | F |
| Current Type | AC | Electrical Durability | 8000 cycle 120 cycles per hour |
| Mechanical Durability | 25000 cycle 240 cycles per hour | Number of Poles | 3P |
| Power Loss | at Rated Operating Conditions per Pole 10.80 W | Rated Current (In) | 160 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC 500 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA | Rated Uninterrupted Current (Iu) | 160 A |
| Release | Ekip C Dip LSI | Release Type | EL |
| Short-Circuit Performance Level | L | Standards | IEC 60947-2 GB/T 14028.2 |
| Sub-type | XT2 | Terminal Connection Type | Fixed Circuit-Breakers |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | Manufacturer ID | 2TFC000947R1001 |