XT2L 160 Ekip LSIG In=160A 3p F F
Product ID:85958
Updated: 2026/4/9

Key Features
- 1Integrate multiple protection functions including overload and earth fault. 2、Ensure reliable operation with a 120kA breaking capacity. 3、Withstand 8000 operations under load for durable performance. 4、Offer easy installation with front terminals and toggle actuator. 5、Meet IEC 60947 standards for global safety compliance.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Net Width | 90 mm |
| Product Net Height | 130 mm | Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 1.12 kg | Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker | Version | F |
| CAD Dimensional Drawing | 1SDH002230A1001 | Connecting Capacity Main Circuit | Busbar 32.5..100 mm² |
| Current Type | AC | Electrical Durability | 120 cycles per hour 8000 cycle |
| Mechanical Durability | 240 cycles per hour 25000 cycle | Number of Poles | 3P |
| Opening Time | CB with SOR 15 ms CB with UVR 15 ms | Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 10.8 W | Rated Current (In) | 160 A |
| Rated Frequency (f) | 50 / 60 Hz | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 15 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA |
| Rated Uninterrupted Current (Iu) | 160 A | Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | Main Circuit M6 | Release | Ekip LSIG |
| Release Type | EL | Short-Circuit Performance Level | L |
| Standards | IEC60947-2 | Sub-type | XT2 |
| Terminal Connection Type | Front | Terminal Type | Bolt |
| Tightening Torque | 6 N·m | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
| UNSPSC | 39120000 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA067933R1 |
Specifications may be subject to change without notice