XT2L 160 Ekip Touch Measuring LSI In=160A 3p F F
Product ID:92289
Updated: 2026/4/4

Key Features
- 1Designed for AC applications with a solid-state release for reliable operation. 2、Equipped with Ekip Touch Measuring LSI technology for accurate current measurement. 3、Mechanical durability of up to 25,000 operations and electrical durability of up to 8,000 operations at 415V AC. 4、Compact dimensions (110 mm x 100 mm x 150 mm) for easy installation in various electrical setups. 5、Meets EU Directive 2011/65/EU and Amendment 2015/863, with CE and GL certificates for safety assurance.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Net Width | 90.0 mm |
| Product Net Height | 130 mm | Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 1.2 kg | Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Version | F | Current Type | AC |
| Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
| Number of Poles | 3P | Power Loss | at Rated Operating Conditions per Pole 10.8 W |
| Rated Current (In) | 160 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA |
| Rated Uninterrupted Current (Iu) | 160 A | Release | Ekip Touch Measuring LSI |
| Release Type | EL | Short-Circuit Performance Level | L |
| Standards | IEC60947-2 GB/T 14028.2 | Sub-type | XT2 |
| Terminal Connection Type | Front | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Manufacturer ID | 2TFN000185A1001 |
Specifications may be subject to change without notice