XT2L160 LSIG R100 WMP 4P

Product ID:70549
Updated: 2026/4/4
ABB XT2L160 LSIG R100 WMP 4P

Key Features

  • 1Handle high short-circuit currents up to 150 kA. 2、Utilize solid-state release technology for reliable operation. 3、Set selective short-circuit protection from 100 to 1000 A. 4、Operate efficiently with 690 V AC voltage compatibility. 5、Meet IEC and EN60947 international safety standards.
Product Details
XT2L160 LSIG R100 WMP 4P
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
120.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
4.04 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
W
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 5.2 W
Rated Current (In)
100 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip LSIG
Release Type
EL
Remarks
ATLAS
Short-Circuit Performance Level
L
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Withdrawable Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH102188R1001

Specifications may be subject to change without notice