XT2L160 LSIG R63 WMP 3P
Product ID:88592
Updated: 2026/4/8

Key Features
- 1Deliver high-performance operation with advanced, reliable technology. 2、Meet stringent IEC, EN, and UL safety and compliance standards. 3、Optimize energy efficiency to minimize loss and maximize uptime. 4、Apply versatility across various demanding industrial settings. 5、Enhance reliability with precise microprocessor fault detection.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Net Width | 90.0 mm |
| Product Net Height | 130 mm | Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 3.32 kg | Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Version | W | Current Type | AC |
| Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
| Number of Poles | 3P | Power Loss | at Rated Operating Conditions per Pole 2.1 W |
| Rated Current (In) | 63 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA |
| Rated Uninterrupted Current (Iu) | 160 A | Release | Ekip LSIG |
| Release Type | EL | Remarks | ATLAS |
| Short-Circuit Performance Level | L | Standards | IEC60947-2 GB/T 14028.2 |
| Sub-type | XT2 | Terminal Connection Type | Withdrawable Circuit-Breakers |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | Manufacturer ID | 2TFH102150R1001 |
Specifications may be subject to change without notice