XT2L 160 TMA125/1250 F F 4P N=100%

Product ID:89221
Updated: 2026/4/7
ABB XT2L 160 TMA125/1250 F F 4P N=100%

Key Features

  • 1Achieve robust protection with up to 100 kA short-circuit breaking capacity. 2、Ensure reliable operation via a thermomagnetic release mechanism. 3、Simplify installation using front terminal connections. 4、Maintain wide voltage compatibility from 690V AC to 500V DC. 5、Meet IEC standards for guaranteed performance and safety.
Product Details
XT2L 160 TMA125/1250 F F 4P N=100%
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
1SDL000190R0001
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
AC/DC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 11.40 W
Rated Current (In)
125 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
L
Standards
IEC 60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFC000615R1001

Specifications may be subject to change without notice