Key Features

  • 1Handle high currents up to 160 A for efficient power distribution. 2、Utilize solid-state release technology for quick, reliable operation. 3、Deploy in three-phase systems with convenient front terminals. 4、Ensure long service life with 8000 electrical and 25000 mechanical cycles. 5、Operate across a versatile voltage range up to 690 V AC.
Product Details
XT2N160 DC TMA160 FF 4P
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle ;240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 16.15 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC 60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SDA123518R1