XT2N160 DC TMA63 FF 4P
Product ID:82055
Updated: 2026/4/14

Key Features
- 1Deliver reliable power with 690V AC and 63A rated current. 2、Ensure safe operation using thermomagnetic release technology. 3、Meet international safety standards with full IEC compliance. 4、Simplify installation with fixed front terminals. 5、Achieve long-lasting performance through 8000-cycle durable design.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product Net Width | 120 mm | Product Net Height | 130 mm |
| Product Net Depth / Length | 82.5 mm | Product Net Weight | 1.6 kg |
| Product Name | Moulded Case Circuit Breaker | Product Type | CB |
| Version | F | Current Type | DC |
| Mechanical Durability | 25000 cycle ;240 cycles per hour | Number of Poles | 4P |
| Power Loss | at Rated Operating Conditions per Pole 4.85 W | Rated Current (In) | 63 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 500 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA | Rated Uninterrupted Current (Iu) | 160 A |
| Release | TMA | Release Type | TM |
| Short-Circuit Performance Level | N | Standards | IEC 60947-2 GB/T 14028.2 |
| Sub-type | XT2 | Terminal Connection Type | Fixed Circuit-Breakers |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | Manufacturer ID | 1SDA123514R1 |
Specifications may be subject to change without notice