XT2N160 DC TMD20 FF 3P

Product ID:90687
Updated: 2026/4/6
ABB XT2N160 DC TMD20 FF 3P

Key Features

  • 1Protect circuits from overcurrents and short circuits. 2、Suit three-phase power distribution systems efficiently. 3、Ensure reliable operation with a thermomagnetic release. 4、Simplify installation using fixed front terminals. 5、Meet international IEC safety standards for compliance.
Product Details
XT2N160 DC TMD20 FF 3P
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle ;240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 1.62 W
Rated Current (In)
20 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC 60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SDA123498R1

Specifications may be subject to change without notice