XT2N160 TMA40/400 WMP 3P

Product ID:91454
Updated: 2026/4/5
ABB XT2N160 TMA40/400 WMP 3P

Key Features

  • 1Deliver up to 65 kA at 220 V AC and 36 kA at 380 V AC. 2、Ensure reliable operation under various load conditions. 3、Simplify installation and reduce wiring errors. 4、Meet IEC, UL, and CSA standards for safety. 5、Withstand 8000 cycles and 25000 cycles of operation.
Product Details
XT2N160 TMA40/400 WMP 3P
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
W
Current Type
AC/DC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 4.4 W
Rated Current (In)
40 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
N
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Withdrawable Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH102342R1001

Specifications may be subject to change without notice