XT2N 160 TMG 125-375 4p F F InN=100%
Product ID:87073
Updated: 2026/4/9

Key Features
- 1Provide robust generator and transformer protection with thermomagnetic release. 2、Ensure high electrical durability with up to 8000 operational cycles. 3、Meet stringent IEC standards for guaranteed safety and performance compliance. 4、Deliver high short-circuit breaking capacity in a four-pole configuration. 5、Simplify installation with front terminal connections for efficient wiring.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Net Width | 120 mm |
| Product Net Height | 130 mm | Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 1.45 kg | Circuit Breaker Type to be Associated | Generator Protection |
| Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker | Version | F |
| CAD Dimensional Drawing | 1SDH002230A1002 | Connecting Capacity Main Circuit | Busbar 32.5..100 mm² |
| Current Type | AC/DC | Electrical Durability | 120 cycles per hour 8000 cycle |
| Mechanical Durability | 240 cycles per hour 25000 cycle | Number of Poles | 4P |
| Opening Time | CB with SOR 15 ms CB with UVR 15 ms | Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 11.4 W | Rated Current (In) | 125 A |
| Rated Frequency (f) | 50 / 60 Hz | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii) | 375 A | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC 500 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA | Rated Uninterrupted Current (Iu) | 160 A |
| Rated Voltage (Ur) | 690 V | Recommended Screw Driver | Main Circuit M6 |
| Release | TMG | Release Type | TM |
| Setting Range | 87.5...125 A | Short-Circuit Performance Level | N |
| Standards | IEC60947-2 | Sub-type | XT2 |
| Terminal Connection Type | Front | Terminal Type | Bolt |
| Tightening Torque | 6 N·m | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
| UNSPSC | 39120000 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA067736R1 |
Specifications may be subject to change without notice