XT2S160 DC TMA80 FF 4P

Product ID:71582
Updated: 2026/4/5
ABB XT2S160 DC TMA80 FF 4P

Key Features

  • 1Deliver 50kA breaking capacity for reliable surge protection. 2、Automatically trip to prevent overheating and ensure safety. 3、Support both AC (690V) and DC (500V) versatile applications. 4、Ensure durability with 120 cycles/hour and 8000-cycle electrical life. 5、Meet IEC standards for international compliance and safety.
Product Details
XT2S160 DC TMA80 FF 4P
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle ;240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 5.8 W
Rated Current (In)
80 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
S
Standards
IEC 60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SDA123537R1

Specifications may be subject to change without notice