XT2S160 DC TMD25 FF 3P
Product ID:92824
Updated: 2026/4/4

Key Features
- 1Handle both AC and DC currents for versatile applications. 2、Utilize thermomagnetic release for safe circuit interruption. 3、Support high current ratings up to 160A. 4、Operate at voltages up to 690V AC and 500V DC. 5、Ensure compliance with international IEC safety standards.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product Net Width | 90 mm | Product Net Height | 130 mm |
| Product Net Depth / Length | 82.5 mm | Product Net Weight | 1.2 kg |
| Product Name | Moulded Case Circuit Breaker | Product Type | CB |
| Version | F | Current Type | DC |
| Mechanical Durability | 25000 cycle ;240 cycles per hour | Number of Poles | 3P |
| Power Loss | at Rated Operating Conditions per Pole 2.00 W | Rated Current (In) | 25 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 500 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA | Rated Uninterrupted Current (Iu) | 160 A |
| Release | TMD | Release Type | TM |
| Short-Circuit Performance Level | S | Standards | IEC 60947-2 GB/T 14028.2 |
| Sub-type | XT2 | Terminal Connection Type | Fixed Circuit-Breakers |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | Manufacturer ID | 1SDA123521R1 |
Specifications may be subject to change without notice