XT2S 160 Ekip Dip LIG In=10A 3p F F
Product ID:84657
Updated: 2026/4/10

Key Features
- 1Ensure reliable short-circuit performance with solid-state release technology. 2、Simplify installation and reduce wiring time via front terminal connection. 3、Achieve long-lasting operation with high electrical durability of 8000 cycles. 4、Meet international safety standards through IEC 60947 compliance. 5、Fit various applications with its compact 90x130x82.5 mm design.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Net Width | 90 mm |
| Product Net Height | 130 mm | Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 1.12 kg | Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker | Version | F |
| CAD Dimensional Drawing | 1SDH002230A1001 | Current Type | AC |
| Electrical Durability | 120 cycles per hour 8000 cycle | Mechanical Durability | 240 cycles per hour 25000 cycle |
| Number of Poles | 3P | Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 0.1 W | Rated Current (In) | 10 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA | Rated Uninterrupted Current (Iu) | 160 A |
| Release | Ekip Dip LIG | Release Type | EL |
| Short-Circuit Performance Level | S | Standards | IEC60947-2 |
| Sub-type | XT2 | Terminal Connection Type | Front |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA100040R1 |
Specifications may be subject to change without notice