XT2S 160 Ekip Dip LSI In=160A 4p F F In=100%

Product ID:87596
Updated: 2026/4/8
ABB XT2S 160 Ekip Dip LSI In=160A 4p F F In=100%

Key Features

  • 1Enhance protection with electronic Ekip DIP LSI trip units. 2、Break short circuits reliably up to 50kA. 3、Configure flexibly for various installations. 4、Upgrade trip units via ABB Ability Marketplace™. 5、Ensure compliance with IEC 60947-1 and 60947-2.
Product Details
XT2S 160 Ekip Dip LSI In=160A 4p F F In=100%
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1002
Current Type
AC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 10.80 W
Rated Current (In)
160 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Release
Ekip Dip LSI
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
XT2
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SDA100049R1

Specifications may be subject to change without notice