XT2V 125 Ekip Dip LSIG In=10A 3p F F UL/CSA

Product ID:87655
Updated: 2026/4/8
ABB XT2V 125 Ekip Dip LSIG In=10A 3p F F UL/CSA

Key Features

  • 1Operate continuously at 100% rating up to 125A with electronic trip unit. 2、Enhance safety using thermal magnetic and electronic trip units. 3、Adjust protection settings for overload, short-circuit, and earth faults. 4、Meet UL 489 and CSA C22.2 standards for reliability. 5、Connect easily with versatile ring-lug or bar connections.
Product Details
XT2V 125 Ekip Dip LSIG In=10A 3p F F UL/CSA
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Current Type
AC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 0.10 W
Rated Current (In)
10 A
Rated Frequency (f)
50/60 Hz
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Release
Ekip Dip LSIG
Release Type
EL
Short-Circuit Performance Level
V
Standards
UL
Sub-type
XT2
Interrupting Rating acc. to UL489
(240 V AC) 200 A (480 V AC) 150 A (600 V AC) 42 A
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SDA122992R1

Specifications may be subject to change without notice