XT2V 160 Ekip Dip LIG In=100A 4p F F

Product ID:90655
Updated: 2026/4/6
ABB XT2V 160 Ekip Dip LIG In=100A 4p F F

Key Features

  • 1Deliver high-performance AC protection with a 100A rated current. 2、Ensure reliable operation using solid-state release technology. 3、Simplify installation and maintenance with front terminal connections. 4、Meet international safety standards via IEC 60947 compliance. 5、Select from various extended product type configurations.
Product Details
XT2V 160 Ekip Dip LIG In=100A 4p F F
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
120.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 4.2 W
Rated Current (In)
100 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 20 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Dip LIG
Release Type
EL
Short-Circuit Performance Level
V
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Front
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFN000076A1001

Specifications may be subject to change without notice