XT2V160 LSI R25 PMP 4P
Product ID:71499
Updated: 2026/4/5

Key Features
- 1Achieve superior electrical durability with up to 25,000 cycles. 2、Utilize the Ekip LSI release for fast and reliable operation. 3、Fit seamlessly into panels with compact 120x82.5x130 mm dimensions. 4、Ensure compliance with IEC safety and performance standards. 5、Suit various industrial applications requiring a 25A four-pole breaker.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Net Width | 120.0 mm |
| Product Net Height | 130 mm | Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 3.27 kg | Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Version | P | Current Type | AC |
| Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
| Number of Poles | 4P | Power Loss | at Rated Operating Conditions per Pole 0.9 W |
| Rated Current (In) | 25 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 20 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 20 kA |
| Rated Uninterrupted Current (Iu) | 160 A | Release | Ekip LSI |
| Release Type | EL | Remarks | ATLAS |
| Short-Circuit Performance Level | V | Standards | IEC60947-2 GB/T 14028.2 |
| Sub-type | XT2 | Terminal Connection Type | Plug-In Circuit-Breakers |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | Manufacturer ID | 2TFH101215R1001 |