XT2V160 LSI R25 PMP 4P

Product ID:71499
Updated: 2026/4/5
ABB XT2V160 LSI R25 PMP 4P

Key Features

  • 1Achieve superior electrical durability with up to 25,000 cycles. 2、Utilize the Ekip LSI release for fast and reliable operation. 3、Fit seamlessly into panels with compact 120x82.5x130 mm dimensions. 4、Ensure compliance with IEC safety and performance standards. 5、Suit various industrial applications requiring a 25A four-pole breaker.
Product Details
XT2V160 LSI R25 PMP 4P
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
120.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
3.27 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 0.9 W
Rated Current (In)
25 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 20 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 20 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip LSI
Release Type
EL
Remarks
ATLAS
Short-Circuit Performance Level
V
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Plug-In Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH101215R1001

Specifications may be subject to change without notice