XT2V 160 TMD 32-320 3p F F
Product ID:85823
Updated: 2026/4/9

Key Features
- 1Achieve a 160 A rated ultimate short-circuit breaking capacity (Icu). 2、Utilize a reliable thermomagnetic release (TMD) for operation. 3、Meet IEC standards for electrical durability and performance. 4、Install and maintain easily with front terminals. 5、Select from the robust XT2 series for high reliability.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Net Width | 90 mm |
| Product Net Height | 130 mm | Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 1.1 kg | Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker | Version | F |
| CAD Dimensional Drawing | 1SDH002230A1001 | Connecting Capacity Main Circuit | Busbar 32.5..100 mm² |
| Current Type | AC/DC | Electrical Durability | 120 cycles per hour 8000 cycle |
| Mechanical Durability | 240 cycles per hour 25000 cycle | Number of Poles | 3P |
| Opening Time | CB with SOR 15 ms CB with UVR 15 ms | Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 2.57 W | Rated Current (In) | 32 A |
| Rated Frequency (f) | 50 / 60 Hz | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii) | 320 A | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC 500 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 3 Poles in Series 100 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 20 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 3 Poles in Series 100 kA | Rated Uninterrupted Current (Iu) | 160 A |
| Rated Voltage (Ur) | 690 V | Recommended Screw Driver | Main Circuit M6 |
| Release | TMD | Release Type | TM |
| Setting Range | 22.4...32 A | Short-Circuit Performance Level | V |
| Standards | IEC60947-2 | Sub-type | XT2 |
| Terminal Connection Type | Front | Terminal Type | Bolt |
| Tightening Torque | 6 N·m | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
| UNSPSC | 39120000 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA067685R1 |
Specifications may be subject to change without notice