XT3N 225 TMF 80-800 4p F F UL/CSA
Product ID:85897
Updated: 2026/4/9

Key Features
- 1Achieve 50 kA interrupting rating at 240 V AC for robust protection. 2、Suit both AC and DC applications including 250/500 V DC systems. 3、Utilize thermomagnetic release (TMF) for precise and reliable operation. 4、Meet stringent UL and CSA safety and reliability standards. 5、Construct with durable materials for extended service life and performance.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Net Width | 140 mm |
| Product Net Height | 150 mm | Product Net Depth / Length | 70 mm |
| Product Net Weight | 2.1 kg | Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker | Suitable for Product Class | SACE Tmax XT |
| Version | F | CAD Dimensional Drawing | 1SDH001295R0483 |
| Connecting Capacity Main Circuit | Busbar 85..192 mm² | Current Type | AC/DC |
| Electrical Durability | 120 cycles per hour 8000 cycle | Mechanical Durability | 240 cycles per hour 25000 cycle |
| Number of Poles | 4P | Opening Time | CB with SOR 15 ms CB with UVR 15 ms |
| Order Multiple | 1 piece | Power Loss | at Rated Operating Conditions per Pole 4.8 W |
| Rated Current (In) | 80 A | Rated Instantaneous Short-Circuit Current Setting (Ii) | 800 A |
| Rated Operational Voltage | 600Y/347 V AC 500 V DC | Rated Uninterrupted Current (Iu) | 225 A |
| Rated Voltage (Ur) | 600Y/347 V | Recommended Screw Driver | Main Circuit M8 |
| Release | TMF | Release Type | TM |
| Setting Range | 80 A | Short-Circuit Performance Level | N |
| Standards | UL489 | Sub-type | XT3 |
| Terminal Connection Type | Front | Terminal Type | Bolt |
| Tightening Torque | 8 N·m | Interrupting Rating acc. to UL489 | (240 V AC) 50 kA (480 V AC) 25 kA (600Y / 347 V AC) 10 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| IDEA Granular Category Code (IGCC) | 4927 >> Molded case circuit breakers | Object Classification Code | Q |
| UNSPSC | 39121616 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA075121R1 |
Specifications may be subject to change without notice