XT3N250 TMD100/1000 PMP 4P

Product ID:71618
Updated: 2026/4/5
ABB XT3N250 TMD100/1000 PMP 4P

Key Features

  • 1Deliver up to 50 kA breaking capacity at 220-240V AC for robust protection. 2、Ensure reliable operation across diverse electrical conditions and loads. 3、Simplify installation and maintenance with easily accessible front terminals. 4、Meet RoHS and WEEE regulations for environmental compliance and sustainability. 5、Support compatibility with 50/60 Hz frequencies and a 690V rated voltage.
Product Details
XT3N250 TMD100/1000 PMP 4P
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC/DC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 6.8 W
Rated Current (In)
100 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 37.5 kA (230 V AC) 37.5 kA (240 V AC) 37.5 kA (380 V AC) 27 kA (415 V AC) 27 kA (440 V AC) 18.75 kA (500 V AC) 15 kA (525 V AC) 9.75 kA (690 V AC) 3.75 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 25 kA (500 V AC) 20 kA (525 V AC) 13 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
250 A
Release
TMD
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
N
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT3
Terminal Connection Type
Plug-In Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH101311R1001

Specifications may be subject to change without notice