XT3N250 TMD200/2000 FF 4P+RC Inst

Product ID:82120
Updated: 2026/4/14
ABB XT3N250 TMD200/2000 FF 4P+RC Inst

Key Features

  • 1Ensure reliable protection with up to 50 kA at 220-240 V AC. 2、Provide quick, safe shutdown via automatic overcurrent tripping. 3、Reduce setup time with easy front-terminal installation. 4、Meet international safety and performance standards for compliance. 5、Guarantee long-term reliability through 25,000 mechanical operations.
Product Details
XT3N250 TMD200/2000 FF 4P+RC Inst
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
140.0 mm
Product Net Height
150.0 mm
Product Net Depth / Length
70.0 mm
Product Net Weight
4.2 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 13.2 W
Rated Current (In)
200 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 37.5 kA (230 V AC) 37.5 kA (240 V AC) 37.5 kA (380 V AC) 27 kA (415 V AC) 27 kA (440 V AC) 18.75 kA (500 V AC) 15 kA (525 V AC) 9.75 kA (690 V AC) 3.75 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 25 kA (500 V AC) 20 kA (525 V AC) 13 kA (690 V AC) 5 kA
Rated Uninterrupted Current (Iu)
250 A
Release
TMD
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
N
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT3
Terminal Connection Type
Front
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100499R1001

Specifications may be subject to change without notice