XT4N 250 Ekip LSI In=250A 3p F F
Product ID:84181
Updated: 2026/4/11

Key Features
- 1Ensure robust performance with up to 25,000 mechanical cycles. 2、Achieve precise trip action via solid-state EKIP-LSI release. 3、Meet safety standards with full IEC60947-2 compliance. 4、Handle faults efficiently in power distribution systems. 5、Operate reliably up to 690V AC and 50/60 Hz.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Net Width | 105 mm |
| Product Net Height | 160 mm | Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 2.323 kg | Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker | Version | F |
| CAD Dimensional Drawing | 1SDH002230A1003 | Connecting Capacity Main Circuit | Busbar 85..200 mm² |
| Current Type | AC | Electrical Durability | 120 cycles per hour 8000 cycle |
| Mechanical Durability | 240 cycles per hour 25000 cycle | Number of Poles | 3P |
| Opening Time | CB with SOR 15 ms CB with UVR 15 ms | Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 16.40 W | Rated Current (In) | 250 A |
| Rated Frequency (f) | 50/60 Hz | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V AC | Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA |
| Rated Uninterrupted Current (Iu) | 250 A | Rated Voltage (Ur) | 690 V AC |
| Recommended Screw Driver | Main Circuit M8 | Release | Ekip LSI |
| Release Type | EL | Short-Circuit Performance Level | N |
| Standards | IEC60947-2 | Sub-type | XT4 |
| Terminal Connection Type | Front | Terminal Type | Bolt |
| Tightening Torque | 8 N·m | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | IDEA Granular Category Code (IGCC) | 4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers |
| Object Classification Code | Q | UNSPSC | 39121616 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
| Manufacturer ID | 1SDA068136R1 |
Specifications may be subject to change without notice