XT4N 250 TMA 250-2500 3p F F
Product ID:83301
Updated: 2026/4/14

Key Features
- 1Deliver up to 36 kA breaking capacity at 415V AC. 2、Adjust the trip unit for customized protection settings. 3、Ensure 8000 operations under load for long service life. 4、Install easily with compact 160x105x82.5 mm dimensions. 5、Meet IEC 60947 standards for safety and reliability.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK108467A6707 | Product Net Width | 105 mm |
| Product Net Height | 160 mm | Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 2.252 kg | Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT | Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker | Version | F |
| CAD Dimensional Drawing | 1SDH002230A1003 | Connecting Capacity Main Circuit | Busbar 85..200 mm² |
| Current Type | AC/DC | Electrical Durability | 120 cycles per hour 8000 cycle |
| Mechanical Durability | 240 cycles per hour 25000 cycle | Number of Poles | 3P |
| Opening Time | CB with SOR 15 ms CB with UVR 15 ms | Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 16.44 W | Rated Current (In) | 250 A |
| Rated Frequency (f) | 50 / 60 Hz | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii) | 1250â¦2500 A | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC 750 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA | Rated Uninterrupted Current (Iu) | 250 A |
| Rated Voltage (Ur) | 690 V | Recommended Screw Driver | Main Circuit M8 |
| Release | TMA | Release Type | TM |
| Setting Range | 175...250 A | Short-Circuit Performance Level | N |
| Standards | IEC60947-2 | Sub-type | XT4 |
| Terminal Connection Type | Front | Terminal Type | Bolt |
| Tightening Torque | 8 N·m | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
| UNSPSC | 39120000 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA068092R1 |
Specifications may be subject to change without notice