XT4N DC 160 TMD125 FF 4P

Product ID:88021
Updated: 2026/4/8
ABB XT4N DC 160 TMD125 FF 4P

Key Features

  • 1Handle robust power with a 160 A rated current. 2、Ensure safety with 65 kA short-circuit breaking capacity at 220 V AC. 3、Rely on TMD technology for stable operation across conditions. 4、Achieve comprehensive protection using the four-pole design. 5、Meet IEC standards for performance and reliability.
Product Details
XT4N DC 160 TMD125 FF 4P
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Product Net Width
140 mm
Product Net Height
160 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
3.5 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 7.40 W
Rated Current (In)
125 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA (750 V DC) 3 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA (750 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
250 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC 60947-2 GB/T 14028.2
Sub-type
XT4
Terminal Connection Type
Fixed Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SDA127158R1

Specifications may be subject to change without notice