IB IL 24 SEG/F-XC-PAC

Product ID:17988
Updated: 2026/4/3
Phoenix Contact IB IL 24 SEG/F-XC-PAC

Key Features

  • 1Creates a protected partial circuit (segment circuit) within an Inline station.
  • 2Operates in extreme ambient temperatures (-40°C to 70°C) and humidity levels (10% to 95%).
  • 3Equipped with a 6.3 A slow-blow fuse for overload and short-circuit protection.
  • 4Meets IP20 standards for dust and water protection.
  • 5Supports 24V DC supply with a range of 19.2V to 30V DC and includes an inline potential distributor.
Product Details
IB IL 24 SEG/F-XC-PAC
Phoenix Contact

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Width
12.2 mm
Height
119.8 mm
Depth
71.5 mm
Note on application
Only for industrial use
Number of interfaces
2
Connection method
Inline data jumper
Transmission speed
500 kbps / 2 Mbps (Can be used in Inline stations with these transmission speeds)
ID code (dec.)
none
ID code (hex)
none
Register length
0 bit
Required parameter data
0 Byte
Required configuration data
0 Byte
Product type
I/O component
Product family
Inline
Type
modular
Article revision
02
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Maximum power dissipation for nominal condition
0 W
Test section
5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min 5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min 7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min 24 V supply (I/O) / functional ground 500 V AC 50 Hz 1 min
Protective circuit
Overload protection, short-circuit protection in the segment circuit; Fuse 5 x 20 with 6.3 A, slow-blowFuses with other values can also be used. The maximum fuse value is 8 A.For fuses with a value greater than 2 A, only slow-blow fuses may be used. Surge protection; Protective elements in the power terminal or the bus coupler Reverse polarity protection; Protective elements in the power terminal or the bus coupler
Fuse
SI 5 x 20 6, 300 AT (in scope of delivery)
Communications power U
7.5 V DC
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 8 A (nominal value) typ. 6 A (The terminal is supplied with a 6.3 A slow-blow fuse. In the event of an increased total current in the potential jumpers U
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Connection name
Inline connector
Connection method
Spring-cage connection
Conductor cross section rigid
0.08 mm² ... 1.5 mm²
Conductor cross section flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Connection method
Spring-cage connection
Conductor cross section, rigid
0.08 mm² ... 1.5 mm²
Conductor cross section, flexible
0.08 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Stripping length
8 mm
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 55 °C (Standard) -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.)
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
GRP_Temperature class
T2 (-40 °C ... 55 °C, EN 50155)
Mounting type
DIN rail mounting

Specifications may be subject to change without notice